IT-DIN-360 Series

IT-DIN-360 Series

360 Watts Single Output Industrial DIN Rail Power Supply Series

  • Universal AC input range(85~264Vac)
  • Support 1+1 or N+1 redundant system(suggest to use redundancy modules.)
  • Built-in active PFC,PF>0.95
  • High efficiency up to 93%
  • Built-in current sharing function
  • Built-in current limiting circuit
  • Output protections: OVP/OLP/SCP/OTP
  • Wide operating ambient temp (-25℃~70℃)
  • 150% peak load capacity
  • Excellent Partial Load Efficiency
  • Built-in DC OK relay contact
  • Can be installed on TS-35/7.5 or TS-35/15
  • 100% full load burn-in test
  • Suitable for critical applications
  • Ultra-slim, 50mm width
  • Free air convection
  • 3 years warranty

Description

360 Watts Single Output Industrial DIN Rail Power Supply Series

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

TECHNICAL SPECIFICATIONS

MODELIT-DIN-360-24IT-DIN-360-36IT-DIN-360-48
OUTPUTDC Output24V36V48V
Rated Current15A10A7.5A
Current Range Note 10~15A0~10A0~7.5A
Ripple and Noise0~70℃≤240mV≤240mV≤480mV
Note 2.-25℃≤480mV≤480mV≤720mV
Voltage ADJ. Range24~28V34~37.5V48~56V
Voltage Accuracy±3.0%
Line Regulation±0.5%
Load Regulation±1.0%
Set-up Time<3S@230Vac
Hold up Time≥20mS(230Vac input, Full load)
Temperature Coefficient±0.03%/ ℃
Overshoot and Undershoot<5.0%
INPUTVoltage Range85Vac~264Vac
Frequency Range47Hz~63Hz
Power Factor (typical)0.99/110Vac 0.95/230Vac full load
Efficiency ( Typical) at 230Vac≥93%≥92.5%≥92.5%
AC Current (max.)<5A/100Vac <2.5A/230Vac
Inrush Current (Typical)<20A/110Vac , <40A/230Vac Cold start
Leakage CurrentInput—output:<0.25mA Input—PG:<3.5mA
110%~150% of rated current, Constant current limiting for some time(150% of rated current, last 3S) then PS
PROTECTIONOver Load
stop working for 7S,after 7S,if the load <=rated current, PS will work normally, auto recovery
29~33V, constant voltage,39~43V, constant voltage58~63V, constant voltage
Over voltage
Auto recoveryAuto recoveryAuto recovery
Over temperature115±5℃, detect on heat sink of power transistor; shut down O/P, auto recovery after temperature goes down.
Short CircuitLong-term mode, auto recovery
Operating amb. Temp. & Hum..-25℃~70℃; 20%~90%RH No condensing
ENVIRONMENTStorage Temp. & Hum..-40℃~85℃; 5%~95%RH No condensing
Safety Standardsmeet UL508, UL60950, EN60950
SAFETY &EMC
Withstand VoltagePrimary-Secondary: 3.0KVac; ≤10mA .Primary-PG: 2.5KVac; ≤10mA. Secondary-PG: 0.5KVac≤20mA.
Isolation Resistance≥100M ohms
EMC EmissionCompliance to EN55022, EN55024, FCC PART 15 Class B
Harmonic CurrentCompliance to EN61000-3-2, CLASS A
EMC ImmunityCompliance to EN61000-4-2,3,4,5,6,8,11; heavy industry level
MTBF (MIL-HDBK-217F)More than 300,000Hrs (25℃, Full load)
OTHERSDimension (W*H*D)50*124*127mm
IT-DIN-360 Series
IT-DIN-360 Series
IT-DIN-360 Series
IT-DIN-360 Series
IT-DIN-360 Series

Product Datasheet

About the author:

Cristian is a brilliant intelligent and great proactivity person and an effective communicator and visionary. He has built a strong (and deserved) reputation as someone with vision, diligence and honor. Cristian is not a simple engineer but he is a real Scientist. His knowledge is not restricted to the area it covers, but its impressive passion for all the technical topics led him to acquire great skills even in areas far from his original studies. Cristian is able to address and solve complex technical problems with excellent results. He is a valuable writer with great scientific background formed with more that 15 years of active research on experimental Nuclear Physics performed in the most famous international research laboratories such as CERN, ESRN, INF. He write about HI-Tech solutions topics and advanced research study applied to industry. He have more than 150 scientific & technical publications. He is also a technical and famous writer in Italy due to his interviews released on the most famous Industrial Italian magazine.